BCH-100230
Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product Brief introduction of the product
-
Dimensions (W*H*D)
1450*2370*1260
-
Rated output power
100kW
-
Rated Capacity
230.4kWh
-
Operating temperature
-20℃~50℃
-
voltage range
684~852V
-
Temperature control method
Battery: Liquid cooling; Electrical compartment: Natural air cooling
Battery parameters | |
Cell Type | LiFePO4 |
Battery specifications | 3.2V/100Ah |
System Configuration | 3P240S |
Rated Capacity | 230.4kWh |
voltage range | 684~852V |
AC grid-connected parameters | |
Rated output power | 100kW |
Overload capacity | 1.1 times long term, 1.2 times 1 minute |
Rated voltage | AC400V |
Rated output current | 145A |
Communication access method | Three-phase four-wire |
Grid voltage range | 400V (-20%~+15%) |
Grid frequency range | 50Hz/60Hz±2.5Hz |
Current total harmonic distortion | ≤3% (full load) |
Power Factor | -0.99~+0.99 |
DC component of current | ≤0.5% |
Charge and discharge conversion time | <100ms |
AC off-grid parameters | |
AC off-grid voltage | AC400V |
AC voltage range | AC400V±3% |
AC off-grid frequency | 50Hz/60Hz |
Off-grid THDU output | ≤3% (linear load) |
Unbalanced load capacity | 100% |
General Parameters | |
Dimensions (WHD) | 1450*2370*1260 |
Maximum weight | 3000kg |
Operating temperature | -20℃~50℃ |
altitude | <2000m |
Temperature control method | Battery: Liquid cooling; Electrical compartment: Natural air cooling |
noise | <75db |
Fire Fighting System | Passive (high temperature trigger) |
Extinguishing agent | Thermal aerosol |
Local display | yes |
Remote backend | yes |